QKJB-K2風(fēng)機(jī)智能綜合保護(hù)裝置
QKJB-K2風(fēng)機(jī)智能綜合保護(hù)裝置的簡單介紹:
一、QKJB-K2風(fēng)機(jī)智能綜合保護(hù)裝置的保護(hù)參數(shù),用戶可查詢和修改這些參數(shù):?
序號?定值名稱?默認(rèn)值?整定參考說明?
1?額定電流?0100A?依據(jù)負(fù)荷的大小設(shè)定額定電流,通常不應(yīng)超過銘牌所示的 大電流。?范圍:?0?~?700A.?
2?速斷定值?09.00?電流互感器一次側(cè)電流的倍數(shù)?范圍:?0?~?9.?
3?速斷延時?0000s?范圍:?0?~?20s.?
4?過載時間檔位?0003?范圍:?1、2、3、4.?
5?欠壓定值?0.500Ue?范圍:?30%?~?100%?Ue.?
6?欠壓延時?01.00s?范圍:?0?~?20s.?
7?過壓定值?1.200Ue?范圍:?105%?~?200%?Ue.?
8?過壓延時?01.00s?范圍:?0?~?20s.?
9?監(jiān)視電壓?50.00V?調(diào)節(jié)零序電壓的靈敏度,范圍:?0?~?99.99V.?
10?監(jiān)視電流?05.00A?調(diào)節(jié)零序電流的靈敏度,范圍:?0?~?10A.?
11?接地延時?01.00s?調(diào)節(jié)接地動作時間,范圍:?0?~?20s.?
12?短路試驗延時?00.10s?范圍:?0?~?20s.?
13?風(fēng)電瓦斯閉鎖延時?00.10s?范圍:?0?~?20s.?
14?備用1?00.10s?范圍:?0?~?20s.?
15?備用2?00.10s?范圍:?0?~?20s.?
16?備用3?00.10s?范圍:?0?~?20s.?
17?備用4?00.10s?范圍:?0?~?20s.?
18?啟動后機(jī)延時?05.00s?順序啟動尾機(jī)延時,范圍:?0?~?20s.?
19?PT?10000V/100V?電壓互感器的變比,用戶請勿改動。?范圍:?0?~?10kV.?
20?CT?0500A/5A?電流互感器的變比,用戶請勿改動。?范圍:?0?~?700A.?
21?裝置地址?0001?高壓啟動器的通訊地址。?范圍:?1?~?127.?
二、QKJB-K2風(fēng)機(jī)智能綜合保護(hù)裝置顯示終端:
1.工作?、若高壓啟動器主機(jī)與顯示終端的通信正常,則工作燈一直閃爍。?
2。事件?、若有保護(hù)事件發(fā)生,事件燈亮。?
3。本機(jī)?、本機(jī)啟動模式,本機(jī)燈亮。?
4。聯(lián)機(jī)?、聯(lián)機(jī)啟動模式,尾機(jī)啟動后,聯(lián)機(jī)燈亮。